Product Overview
The wireless transmission alarm system is composed of wireless transmit modules, detection instruments and receiving control cabinets. It realizes long-distance gas detection without field wiring at the detection side, bringing simple installation and operation. The receiving terminal uses a large touch screen to display gas concentration readings, and supports query of alarm records and trend curves.
Two wireless transmission modes are available: LoRa and 4G IoT to meet diverse application requirements. The LoRa solution delivers a transmission distance over 350 meters and incurs no network service charges. The 4G IoT option is suitable for ultra-long-distance transmission, available nationwide with no distance limit.

Product Features
The system adopts original imported sensors.
Equipped with an LCD screen, it delivers clear readings.
It supports intelligent temperature compensation, zero point compensation and fault alarm indication.
With wireless networking capability, detectors can connect to wireless controllers.
The smart solar charging system with built-in lithium battery removes the need for on-site wiring.
The product holds national explosion-proof certification.
The 4G IoT version integrates built-in GPS for real-time positioning.
Users can set up electronic geofences; an alarm will trigger once out of the predefined zone to prevent device loss.
Battery lifespan: rechargeable battery lasts 3 months on a single charge. Maintenance-free non-rechargeable batteries can operate for more than 3 years under normal conditions.
Total power consumption of the detector is less than 10 mW. It supports remote debugging, remote alarm mute and remote zero calibration.
The client platform enables users to check alarm records and historical trend curves.
Each gas detector of the 4G IoT version comes with 10 years of 4G data traffic. Customised packages are available upon request.
Technical Parameters
| Item | Specification | Item | Specification |
|---|---|---|---|
| Detection Gas | Combustible gases, toxic gases (sensor type configurable per customer requirements) | Wireless Range | ≥ 350 m |
| Detection Principle | Electrochemical, catalytic combustion, point-type infrared, photoionization | Operating Temperature | -40°C ~ 70°C |
| Detection Range | Customized according to customer requirements | Explosion-proof Certification | Ex db ib IIC T6 Gb; Ex tb IIIC T80°C Db |
| Accuracy | ±3% LEL (combustible gases); ±3% FS (toxic gases) | Protection Rating | IP66 |
| Sensor Life | Combustible gases (clean atmosphere) ≥ 3 years; Toxic gases (clean atmosphere) ≥ 2 years | Ambient Humidity | < 95% RH (no condensation) |
| Indication Error | ±3% FS | Pressure Range | 86 ~ 106 kPa |
| Resolution | 1% LEL | Power Supply | Solar charging + lithium polymer battery |
| Response Time | ≤ 30 s | Solar Panel Dimensions | 540 × 450 mm |
| Repeatability | 2% | Solar Panel Power | 40 W |
| Alarm Sound Level | ≥ 110 dB | Body Material | Cast aluminum + stainless steel |
| Alarm Method | Wireless, integrated sound-light, cloud alarm | Instrument Dimensions | 230 × 180 × 105 mm |
| Wireless Frequency | LoRa 433 MHz | Display | LCD screen |
| Alarm Levels | Two levels | Sampling Method | Pump suction / diffusion |
| Item | Specification |
|---|---|
| Signal Input | LoRa |
| Connected Points | Number of detector connection points customizable per requirements |
| Installation Method | Wall-mounted |
| Installation Location | Indoor |
| Operating Voltage | 220 VAC ±10%; DC ≤ 24 V |
| Backup Power | Optional built-in UPS, backup duration ≥ 0.5 h |
| Concentration Display | Real-time on-site concentration display |
| Alarm Method | Sound-light alarm, voice alarm ≥ 85 dB, alarm response time ≤ 10 s, manual alarm reset function |
| Operation | Touch screen |
| Data Query | 1999 concentration / fault alarm records |
| Signal Output | 1-channel standard RS485 output + 2-channel switch output (multi-channel customizable) |
| Ambient Temperature | (-10 ~ +50) °C |
| Standard | GB 16808 |